Description
Product introduction:
Model: AI/MI
Name: Actuator’s Gear Mechanism(Including Magnetic Pulse Counter)
Manufacturer: Shanghai Automation Instrumentation Co., Ltd.
Application: AI/MI Actuator’s Gear Mechanism(Including Magnetic Pulse Counter) of Shangyi electric actuator
1, AI / MI series intelligent electric actuators is the introduction of product ROTORK A / M Series actuators , based on using the most advanced ultra- large scale integrated circuit developed from the new generation of intelligent , digital, full Chinese menu display , remote operation of the electric actuator.OutlineStandard code and the name of the product performed : Q / YXBM 233 -2004 "AI / MI series intelligent electric actuators "1, AI / MI intelligent electric actuators are the main features :Classic mechanical torque sensor, stable performance , reliable work.Hall Effect pulse digitized displacement sensor high level of accuracy , adaptability.Ultra large scale integrated chip , the executing agency with a powerful functionality.And the whole Chinese character display , menu -driven operation, highlights the debugging simple, easy operation advantages.Dual seal design, no through- shaft design and need not lid , set and operate by remote control, it is an absolute guarantee of protection IP68
2, AI / MI intelligent electric actuator functions:Remote control setting functionActuator display functionTravel limit protectionTorque limit protectionStatus indication contact functions1 ) Limit midway2 ) The actuator is open3 ) The actuator is closed4) The actuator is running5 ) Local Stop6 ) local control7 ) Remote control8 ) Open interlock9 ) Close Interlock10 ) handwheel operation11 ) open the valve torque trip12 ) off the valve torque trip13 ) stroke torque tripValve alarm functiona, Guan direction over torqueb, over torque OPENc, omni-directional over-torque2) The stall alarm functiona, Guan direction stallb, opening direction stallc, omnidirectional stallControl and alarm functions1 ) Emergency (ESD) protection alarm2 ) off the signal alarm protectionActuator alarm function1) The motor overheating protection2 ) Low battery protection3) Power failure protection4 ) power phase , out of phase protection5 ) Internal System Fault Protection6 ) The current valve position signal of loss of protection7 ) In situ wiring fault alarm
● Operating system:
1) AI (S2 reversible, intermittent operation, 25% of On-rate, turning often ≤630 times / hour)
2) MI (S4 reversible, intermittent operation, 25% of On-rate 630 times / hour ≤ turned frequency ≤1200 times / hour)
● Input signal: 1) Analog signal: 4 ~ 20mA.DC input impedance 250Ω
2) the pulse switch signal ≥150ms3) Profibus-DP, HART (optional)
● Output signal: 1) 4-20mA.DC load impedance ≤750Ω
2) Profibus-DP, HART (optional)
● mechanical output: 1) AI multi-turn loop ≥6
2) MI ≥6 ring multi-turn
3) AI stroke 0 ~ 90 ° angle
4) MI Rotary 0 ~ 90 °
5) MIL straight trip ≤100mm 34 ~ 8000Nm 17 ~ 544Nm 300 ~ 60000Nm 116 ~ 6884Nm 7.94 ~ 41.4kN
● basic error: 1) AI, MI multi-turn electric actuators ≤ ± 1%
2) AI, MI rotary electric actuator ≤ ± 1%
3) MIL straight stroke electric actuator (stroke ≥25mm) ≤ ± 1%
● Dead:Adjustable from 0.1 to 9.9% (the default setting is 0.5%)
● midway Limit:1) The open limit setting range of 60% to 100%
2) closed limit setting range is from 0% to 40%
● mechanical clearance: 1) AI, MI multi-turn electric actuators ≤1 °
2) AI, MI rotary actuators ≤1 °
3) MIL straight stroke electric actuator (stroke ≥25mm) ≤1mm
● Do not Run Time: 0 to 99 seconds adjustable
● Power supply: three-phase three-wire system, 380V.AC ± 10%, 50Hz ± 1%
● Explosion levels: 1) Remote control - intrinsically safe ExibⅡBT4 (Flameproof)
2) Actuator --- flameproof ExdⅡBT4
● Output contact capacity: 250V.AC, 5A; 30V.DC, 5A (bus products 220V.AC, 0.5A; 30V.DC, 1A)
● environmental conditions: 1) Ambient temperature: -25 ℃ ~ + 70 ℃ (Explosion-of -20 ℃ ~ + 60 ℃)
2) Relative humidity: 5% to 95%
3) Atmospheric pressure: 86 ~ 106kPa
4) Air media: non-corrosive gases in ambient air
● interference indicators:1) external magnetic field ≤400A / m, 50Hz
2) common mode interference 250V, 50HzAC signal frequency
3) Series-mode interference effective value of 1V is 50Hz, phase 0 ~ 360 °
4) Electrostatic Discharge: 4kV
5) Electrical fast instant burst: power supply terminal 1000V; the signal input: 500V
6) RFI: 80 ~ 1000MHz frequency testing ground for strong 3V / m, distance 1m
7) Surge: 1kVNOTE: If you have other technical requirements, please contact us, we will try to accommodate you.
SHANGHAI AUTOMATION INSTRUMENTATION CO. LTD
NO. 11 AUTOMATION INSTRUMENTATION FACTORY
SHANGHAI AUTOMATION INSTRUMENTATION CO. LTD
NO. 11 AUTOMATION INSTRUMENTATION FACTORY
Shanghai Yi Electric Actuator
SHANGYI ELECTRIC ACTUATOR
SHANGYI BRAND